AC/DC Current Transducer DHRC420 IPN = 100 .. 1000 A
The transducer for the electronic measurement of DC & distorted AC waveform currents, with galvanic isolation between the primary circuit (power) and the secondary circuit (measurement). True RMS 4-20 mA current output.dat
Primary Nominal | Primary AC Current | Output current | Type | |||
DC & AC Current | Max. Peak Value 1) |
|
|
| ||
| IPN | (A.t.RMS) | IP (A) | IOUT | (mA DC) |
|
|
| 100 | 600 |
| 4-20 | DHR 100 C420 |
|
| 200 | 600 |
| 4-20 | DHR 200 C420 |
|
| 300 | 1000 |
| 4-20 | DHR 300 C420 |
|
| 400 | 1000 |
| 4-20 | DHR 400 C420 |
|
| 500 2) | 1800 |
| 4-20 | DHR 500 C420 |
|
| 600 2) | 1800 |
| 4-20 | DHR 600 C420 |
|
| 1000 2) | 1800 |
| 4-20 | DHR 1000 C420 |
RL | Load resistance |
|
|
| < 300 | W |
VC | Supply voltage |
|
|
| + 20 .. 50 | V DC |
IC | Current consumption |
|
|
| 30 mA + IOUT |
|
ISL | Output current limitation |
|
|
| < 25 | mA |
ÎP | Overload capability (Ampere Turns) | 30000 | A.t | |||
|
|
|
|
|
| |
Performance data |
|
|
|
|
| |
X | Accuracy @ IPN, TA = 25°C (excluding offset) | < ± 1 | % of IPN | |||
eL | Linearity error (1% of IPN | .. ± IPN) | < ± 1.0 | % of IPN | ||
IOE | Electrical offset current, | TA | = 25°C | 4 | mA | |
TCIOE | Temperature coefficient of | IOE | ( 0..+60 °C) | ± 3.2 | mA/K | |
|
|
|
| (-40..+70 °C) | ± 6.4 | mA/K |
TCIOUT | Temperature coefficient of IOUT | (% of reading) | ± 0.1 | %/K | ||
tr | Response time to 90 % of IPN step | < 150 | ms | |||
BW | Frequency bandwidth (± 1 dB) |
| DC 20..6000 | Hz | ||
|
|
|
|
|
| |
General data |
|
|
|
|
| |
TA | Surrounding operating temperature | - 40 .. + 70 | °C | |||
TS | Surrounding storage temperature | - 40 .. + 85 | °C | |||
m | Mass |
|
|
| 260 | g |
IPxx | Protection degree |
|
|
| IP20 |
|
Notes : 1) The Max. Peak AC Current is the highest peak level of the primary signal that is taken into account for accurate True RMS calculation. Yet the device is designed for maximum continuous True RMS value equal to IPN, whereas the output is limited by the above specified output limitation.
2) According to the UL 508 Standard for Safety for Industrial Control Equipment the primary current must not exceed 475 A.t.RMS through the transducer hole.
Features
●● VFD and SCR waveforms current measurement
●● True RMS output
●● 4-20 mA current output ●● Panel mounting
●● Eliminates insertion loss
●● Isolated plastic case recognized according to UL94-V0
Advantages
●● Large aperture for cable up to Ø32mm
●● High isolation between primary and secondary circuits
●● Easy installation
Applications
●● VFD Controlled Loads
VFD output indicates how the
motor and attached load are
operating.
●● SCR Controlled Loads Acurate measurement of phase angle fired or burst fired (time proportioned) SCRs. Current measurement gives faster response than temperature measurement.
●● Switching Power Supplies and
Electronic Ballasts
True RMS sensing is the most accurate way to measure power supply or ballast input power.
Application domain
●● Energy and Automation
Vb
Rated isolation voltage rms 3) 300 V
according to the standard IEC 61010-1 and with the following conditions:
V | Rms voltage for AC isolation test 4), 50 Hz, 1min | 4.0 | kV |
d | Creepage distance | 7.2 | mm |
dCp | |||
dCl | Clearance distance | 7.2 | mm |
CTI | Comparative tracking index (Group I) | > 600 |
|